Wall Louver
-
Wall louvers are sized to match California
Turbo Building Vault Fans, and designed to prevent rain from
entering through the louver.
-
Wall louvers are constructed of galvanized
steel with 1/2" mesh screen inside.
-
Louvers can be used for either the air inlet
or air discharge side of a vault.
|
Wall
Louver |
MODEL |
FAN SIZE |
WALL OPENING |
LOUVER
DINENSIONS |
LVR12GV
LVR18GV
LVR24GV |
BVF12
BVF18
BVF24 |
18 X 18
24 X 24
30 X 30 |
17-3/4 X 17-3/4
23-3/4 X 23-3/4
29-3/4 X 29-3/4 |
|
|
Fire Damper
-
Fire dampers are rated by "Underwriters
Laboratories®" for three hours when used in a three
or four hour rated wall or partition assembly, and for 1-1/2
hours when used in a one or two hour rated wall or partition
assembly. Fire damper must be mounted vertically. Fire damper
designed for interior walls.
-
Fire dampers are built of galvanized steel.
-
IMPORTANT! Because the fire
damper utilizes a fusible link that senses heat from the fire
and deploys the damper curtain; FIRE DAMPERS MUST BE MOUNTED
ON THE AIR DISCHARGE SIDE OF THE VAULT. If the fire damper is
mounted on the air inlet side, it will not deploy in a fire
situation because the fusible link will be cooled by outside
air.
|
Fire
Damper |
MODEL |
FAN SIZE |
WALL OPENING |
DINENSIONS
Height x Width |
FRD12GV
FRD18GV
FRD24GV |
BVF12
BVF18
BVF24 |
18 X 18
24 X 24
30 X 30 |
17-3/4 X 21
23-3/4 X 27
29-3/4 X 33 |
|
|
Building Vault Fan Fire Shut-down Device
- Heat Detector
UL® Listed 521
Normal operating temperature 100° - 150° F
Trigger at 200° F or temperature rise in excess of 15°
F per minute
- Rated 15 A, 125V
|